Revolutionizing Air Quality and Patient Safety in Operation Theatres Biomotion introduces the Ductless Laminar Airflow (LAF) System, a state-of-the-art solution designed to create a filtered and sterile air tent over the operating table. This innovative technology provides the highest standards of air quality and patient safety, ensuring a controlled, sterile environment for critical surgical procedures. Features and Benefits of the Ductless Laminar Airflow System
1. Filtered and Sterile Air Tent:
• The system generates a Class 1 (1–10 particles) air quality zone near the HEPA filter, delivering ultra-clean air to the surgical site.
• Contaminated air is kept outside the sterile tent, ensuring an aseptic environment.
• Air quality levels across the OT are stratified for safety:
• Class III (100–1,000 particles) and Class IV (1,000–10,000 particles) are measured on the periphery, meeting operational standards while prioritizing the surgical zone.
2. Energy-Efficient Blower System:
• Powered by a 0.18 kW blower, the system ensures a consistent airflow velocity of 90–120 FPM at the grill or diffuser level. 3. Ease of Maintenance:
• Designed for daily upkeep directly from within the OT, ensuring operational efficiency without the need for complex procedures.
4. Integrated Germicidal UV Protection:
• Equipped with UV light, the system inhibits the growth of germs and fungi on the HEPA filter, extending its lifespan to 2–3 years.
5. Advanced Monitoring:
• A digital differential pressure gauge provides real-time monitoring of the HEPA filter’s condition, with audio-visual alerts for timely replacement.
• The system displays temperature and humidity levels on the LAF control panel, allowing precise environmental control. Biomotion’s Ductless Air Handling Unit (AHU) A Groundbreaking Innovation in Healthcare Air Management For the first time in healthcare history, Biomotion proudly introduces its Ductless Air Handling Unit (AHU). Built with an aluminum double-skin acoustic panel body and a thermal break, this AHU is designed to adhere strictly to NABH guidelines, ensuring superior air quality, infection control, and operational safety in OTs. Key Features and Compliance with NABH Guidelines
1. HEPA Filtration (0.3 Micron):
• Equipped with High-Efficiency Particulate Air (HEPA) filters for sterilized air delivery.
• Air is supplied via terminal HEPA filters in the ceiling, or at the AHU level when terminal placement is not feasible.
• The filtration zone extends 1 foot (304.8 mm) on all sides of the OT table, covering the surgical team and ensuring comprehensive sterility.
2. Air Changes and Ventilation:
• The unit ensures compliance with NABH’s minimum requirement of 20 air changes per hour (ACH) through precise control of supply air volume (measured in cubic feet per minute, CFM).
3. Positive Pressure Maintenance:
• Integrated pressure dampers regulate fresh air intake and ensure positive pressure (≥15 Pa) within the OT, preventing cross-contamination from adjoining spaces.
4. Temperature Control (18–21°C):
• The system maintains a stable OT temperature range of 18–21°C, supported by a standby outdoor unit for seamless cooling and heating.
• Airflow is routed through the AHU, not LAF, minimizing the risk of hypothermia in patients during surgical procedures.
5. Air Recirculation and Sterility:
• Recirculated air ensures consistent sterility by removing contaminants, reducing energy costs, and maintaining OT cleanliness.
6. Simplified Maintenance:
• Pre-filters are positioned at the lower end of the AHU for easy access, simplifying routine cleaning and minimizing downtime. Why Choose Biomotion’s Systems? Biomotion’s Ductless Laminar Airflow System and Ductless AHU are designed to meet the highest standards of operational efficiency, regulatory compliance, and patient safety.
• Regulatory Compliance: Fully adheres to NABH guidelines for air quality, pressure, temperature, humidity, and airflow.
• Enhanced Patient Safety: Sterile airflow prevents infections and supports optimal surgical outcomes.
• Energy Efficiency: Low-power systems minimize energy consumption while delivering high performance.
• Advanced Monitoring: Real-time feedback and alerts ensure proactive maintenance and reliable operation.
• Custom Solutions: Tailored to the unique needs of healthcare facilities for scalability and flexibility. Experience Excellence with Biomotion At Biomotion, we are committed to delivering cutting-edge solutions that redefine air quality standards in healthcare.
Invest in safety, reliability, and compliance—because patient care deserves the best.